Description
4-wire photoelectric smoke detector with NC/NO relay output and auto reset, for 12 or 24 V DC, to EN 54-7.
| Detection | Smoke, photoelectric element |
|---|---|
| Wiring | 4-wire, NC/NO relay output by jumper |
| Reset | Automatic (auto reset), under 1 s |
| Supply voltage | 12/24 V DC |
| Current draw | 30/40 mA alarm / 40 µA standby |
| Standard | EN 54-7, UL 268 |
Product description
SD388-4AR · Sentek
4-wire photoelectric smoke detector with NC/NO relay output and auto reset, for 12 or 24 V DC, to EN 54-7.
The SD388-4AR is a conventional photoelectric smoke detector for alarm or fire panel zones. It uses 4 wires: 2 for the 12 or 24 V DC supply and 2 for the relay contact, which is set to NC or NO by jumper.
With auto reset, the detector returns to standby by itself once the smoke clears, in under 1 s, with no need to cut the power. The LED flashes every 1–3 s in standby and stays steady red in alarm.
Start-up time is up to 30 s. The relay contact is rated 1 A / 30 V DC or 0.5 A / 125 V AC. The detector is 102 mm in diameter and 43 mm high with its base.
| 1 | Photoelectric sensing. With advanced detection algorithms. |
|---|---|
| 2 | NC/NO relay output. Set by jumper, 1 A / 30 V DC. |
| 3 | Auto reset. Returns to standby by itself after an alarm. |
| 4 | Status LED. Flashes in standby, steady in alarm. |
| 5 | 12 or 24 V DC. Powered from an alarm or fire panel. |
Technical specifications
SD388-4AR
| DETECTION | |
|---|---|
| Detection | Smoke, photoelectric element |
| Sensitivity | 0.08–0.14 dB/m (EN) |
| Processing | Advanced detection algorithms |
| OUTPUTS AND INDICATIONS | |
| Wiring | 4-wire, relay output |
| Contact mode | NC/NO by jumper |
| Relay rating | 1 A / 30 V DC, 0.5 A / 125 V AC |
| Reset | Automatic, under 1 s |
| LED | Flashes every 1–3 s in standby, steady red in alarm |
| POWER | |
| Supply voltage | 12/24 V DC |
| Standby current | 40 µA |
| Alarm current | 30/40 mA (12/24 V) |
| Start-up time | Up to 30 s |
| ENVIRONMENT AND MECHANICAL | |
| Operating temperature | −10 to +50 °C |
| Humidity | 0–95 % RH, non-condensing |
| Dimensions | Ø102 × 43 mm with base |
| Weight | 135 g with base |
| CERTIFICATION | |
| Standards | EN 54-7, UL 268 |