FD718-4 – 4-wire UV flame detector

Description

Product description

FD718-4 · Sentek

Ultraviolet (UV 185–260 nm) flame detector with a Hamamatsu UVTRON sensor, 6 m range, 4-wire connection and NC/NO relay output, compatible with EN 54-10.

The FD718-4 detects the ultraviolet radiation of a flame in the 185–260 nm band with a Hamamatsu UVTRON sensor. It sees a 2 cm flame at up to 6 m, with high sensitivity and wide directivity, and uses detection and discrimination algorithms for a reliable response.

It is the 4-wire version of the FD718 range: it runs on 12 or 24 V DC and signals an alarm through a Form A relay contact rated 2 A / 30 V DC or 0.5 A / 125 V AC, set to NC or NO by jumper. It draws up to 220 μA in stand-by and up to 30 mA in alarm, and needs up to 30 seconds to start after power-up.

In normal operation the two red LEDs blink every 5 seconds and in alarm they stay lit; the alarm is reset by removing power. It also detects steady flames without flicker, such as a lighter or a blue gas flame, and suits engine rooms, factories, garages, warehouses and hospitals. It should not be fitted outdoors or near sparks, welding or UV lamps, and the optical window must be kept free of dust and oil. It fits a low-profile base (102 mm diameter, 40 mm high with the base) and works from 0 to 50 °C.

STANDARD FUNCTIONS
1UVTRON sensor. Hamamatsu, ultraviolet band 185–260 nm.
26 m range. For a 2 cm flame, with wide directivity.
3Relay output. 2 A / 30 V DC contact, NC or NO by jumper.
412/24 V DC supply. 4-wire connection to an intruder or fire panel.
5LED indication. Blinks every 5 seconds in stand-by, steady red in alarm.

Technical specifications

FD718-4

DETECTION
DetectionUltraviolet (UV)
Spectral response185–260 nm
SensorUVTRON, Hamamatsu
Range6 m (2 cm flame)
Start-up timeUp to 30 seconds
OUTPUTS AND INDICATIONS
Wiring4-wire, relay output
Relay contactForm A, 2.0 A / 30 V DC, 0.5 A / 125 V AC
Contact modeNC or NO by jumper
LED2 red: blink every 5 s in stand-by, steady in alarm
Alarm resetBy removing power
POWER
Supply voltage12/24 V DC
Stand-by currentUp to 220 μA
Alarm currentUp to 30 mA
Start-up currentUp to 260 μA
Maximum permissible current80 mA
CERTIFICATION AND MECHANICAL
StandardCompatible with EN 54-10
Operating temperature0 to 50 °C
Humidity0–95% RH, non-condensing
DimensionsØ102 × 40 mm with base
Weight130 g with base

Documents

1 PDF file · English

TypeTITLELANGUAGEFORMATOpen
PDFDatasheetFD718-4 - Datasheet EN.pdfEnglishPDF · 0.2 MBDownload the file Datasheet