Description
4-wire heat detector for a fixed temperature of 57 °C or a rapid temperature rise (rate-of-rise), with NC/NO relay output, auto reset and 12/24 V DC supply, compatible with EN 54-5.
| Detection | Fixed temperature 57 °C or rate-of-rise |
|---|---|
| Wiring | 4-wire, NC/NO relay output |
| Reset | Automatic (auto reset) |
| Supply voltage | 12/24 V DC |
| Current | 45 μA stand-by, 30 mA in alarm |
| Standard | Compatible with EN 54-5 and UL521 |
Product description
HD951-4AR · Sentek
4-wire heat detector for a fixed temperature of 57 °C or a rapid temperature rise (rate-of-rise), with NC/NO relay output, auto reset and 12/24 V DC supply, compatible with EN 54-5.
The HD951-4AR alarms when the room temperature reaches 57 °C or rises quickly (rate-of-rise, class 2 to EN 54-5 or 8 °C/min to UL521). It uses detection and discrimination algorithms for a fast, reliable response, and the sensor head never needs replacing.
It connects to an alarm panel with 4 wires: it runs on 12 or 24 V DC and the Form A relay contact (1 A / 30 V DC) is set to NC or NO by jumper. The auto reset (AR) function restores it by itself after an alarm, as security systems need, without removing power.
It draws up to 45 μA in stand-by and up to 30 mA in alarm, and needs up to 30 seconds to start after power-up. The LED shows normal operation and lights steady red in alarm. It has a slim design with a low-profile base.
| 1 | Dual detection. Fixed temperature of 57 °C or rapid rise in temperature. |
|---|---|
| 2 | Relay output. 1 A / 30 V DC contact, NC or NO by jumper. |
| 3 | Auto reset. Restores itself after an alarm. |
| 4 | Low current. 45 μA in stand-by, 12 or 24 V DC. |
| 5 | LED indication. Normal operation in stand-by, steady red in alarm. |
Technical specifications
HD951-4AR
| DETECTION | |
|---|---|
| Fixed temperature | 57 °C |
| Rate-of-rise | Class 2 (EN 54-5) or 8 °C/min (UL521) |
| Sensor | Durable head, no replacement needed |
| Start-up time | Up to 30 seconds |
| OUTPUTS AND INDICATIONS | |
| Wiring | 4-wire, relay output |
| Relay contact | Form A, 1.0 A / 30 V DC, 0.5 A / 125 V AC |
| Contact mode | NC or NO by jumper |
| Reset | Automatic (auto reset) |
| LED | Normal operation in stand-by, steady red in alarm |
| POWER | |
| Supply voltage | 12/24 V DC |
| Stand-by current | Up to 45 μA |
| Alarm current | Up to 30 mA |
| Surge current | Up to 100 μA |
| CERTIFICATION AND MECHANICAL | |
| Standards | Compatible with EN 54-5 and UL521 |
| Operating temperature | −10 to +50 °C |
| Humidity | 0–95% RH, non-condensing |
| Dimensions | Ø102 × 43 mm with base |
| Weight | 125 g with base |
Documents
1 PDF file · English
| Type | TITLE | LANGUAGE | FORMAT | Open |
|---|---|---|---|---|
| ManualHD951-4AR - Manual EN.pdf | English | PDF · 0.1 MB | Download the file Manual |