4-wire combustible gas detector (natural gas / methane and LPG) with a Figaro semiconductor sensor, alarm below 10% LEL, NC/NO relay output and a 75 dB buzzer.
| Gas | Natural gas (methane) and LPG |
|---|---|
| Sensor | Figaro semiconductor |
| Alarm threshold | Below 10% LEL |
| Wiring | 4-wire, NC/NO relay output |
| Buzzer | 75 dB at 3 m in alarm |
| Supply voltage | 12/24 V DC |
Product description
GD518NR · Sentek
4-wire combustible gas detector (natural gas / methane and LPG) with a Figaro semiconductor sensor, alarm below 10% LEL, NC/NO relay output and a 75 dB buzzer.
The GD518NR detects a build-up of natural gas (methane) or liquefied gas (LPG) with a Figaro semiconductor sensor and digital processing with detection and discrimination algorithms. It alarms below 10% of the lower explosive limit (LEL); sensitivity is calibrated to UL1484/2075 or EN50194. It is mounted high, up to 30 cm below the ceiling, for methane, or low, up to 30 cm above the floor, for LPG.
This is the 4-wire relay version: it runs on 12 or 24 V DC from an alarm panel or power supply, and the relay contact (NO or NC, 1 A / 30 V DC) can signal a panel zone or drive a fan or gas shut-off valve. It draws 90 mA in stand-by and 80 mA in alarm at 12 V (56 / 50 mA at 24 V).
Two LEDs, visible through 360°, show the status: green in normal operation, flashing red in alarm. At the same time the built-in buzzer sounds at over 75 dB at 3 m, with automatic reset. The function test is done with a magnet and the mounting base is included.
| 1 | Figaro sensor. Semiconductor for natural gas and LPG, alarm below 10% LEL. |
|---|---|
| 2 | Relay output. NO or NC contact, 1 A / 30 V DC, for a panel, fan or valve. |
| 3 | Buzzer. Over 75 dB at 3 m, with automatic reset. |
| 4 | LED indication. Green in stand-by, flashing red in alarm, visible through 360°. |
| 5 | Magnet test. Function test without opening the detector. |
Technical specifications
GD518NR
| DETECTION | |
|---|---|
| Gas | Natural gas (methane), LPG |
| Sensor | Figaro semiconductor |
| Alarm threshold | Below 10% LEL |
| Sensitivity calibration | UL1484/2075 or EN50194 |
| Mounting position | Within 30 cm of the ceiling (methane) or floor (LPG) |
| OUTPUTS AND INDICATIONS | |
| Wiring | 4-wire, relay output |
| Relay contact | NO or NC, 1.0 A / 30 V DC, 0.5 A / 125 V AC (resistive load) |
| Buzzer | Over 75 dB at 3 m, automatic reset |
| LED | Green in stand-by, flashing red in alarm |
| Test | Function test with a magnet |
| POWER | |
| Supply voltage | 12/24 V DC |
| Stand-by current | 90 mA (12 V) / 56 mA (24 V) |
| Alarm current | 80 mA (12 V) / 50 mA (24 V) |
| Power | 2 W |
| MECHANICAL | |
| Operating temperature | −10 to +50 °C |
| Humidity | 30–95% RH |
| Dimensions | Ø98 × 43 mm |
| Weight | 170 g with base |
| Included | Mounting base |
Documents
3 PDF files · English
| Type | TITLE | LANGUAGE | FORMAT | Open |
|---|---|---|---|---|
| ManualGD518NR - Manual EN.pdf | English | PDF · 1.6 MB | Download the file Manual | |
| DatasheetGD518NR - Datasheet.pdf | — | PDF · 0.1 MB | Download the file Datasheet | |
| DatasheetGD518NR - Datasheet EN.pdf | English | PDF · 0.1 MB | Download the file Datasheet |