Description
Photoelectric smoke detector and rate-of-rise heat detector (57 °C or a rise of 8.3 °C/min) in one unit, 4-wire with relay output, for 12 V DC.
| Detection | Photoelectric smoke + rate-of-rise heat (57 °C or 8.3 °C/min) |
|---|---|
| Wiring | 4-wire (2 power, 2 relay) |
| Relay output | NC/NO by jumper, 1 A / 30 V DC |
| Supply voltage | 12 V DC (10–13.8 V) |
| Current draw | 30 mA alarm / 80 µA standby |
| Certification | EN 54-7 (smoke), EN 54-5 (heat), UL 268 |
Product description
SD119-4H-12 · Sentek
Photoelectric smoke detector and rate-of-rise heat detector (57 °C or a rise of 8.3 °C/min) in one unit, 4-wire with relay output, for 12 V DC.
The SD119-4H-12 combines a photoelectric smoke detector and a rate-of-rise heat detector, which alarms at 57 °C (135 °F) or when the temperature rises by 8.3 °C (15 °F) per minute. The two circuits work independently and their outputs are OR-connected, so an alarm comes from either smoke or heat. It uses 4 wires: 2 for the 12 V DC supply and 2 for the relay contact.
The relay is factory-set to NO and changes to NC with a jumper on the board, next to the relay. The red LED flashes every 1–3 s in standby and stays on in alarm. Start-up time is up to 30 s, and after a smoke alarm the reset takes up to 30 s.
It mounts on the ceiling at least 15 cm from a wall, or on a wall 10–30 cm below the ceiling. The base fits straight onto a junction box with no adaptor, and up to 30 detectors go on one loop. It is not recommended where air speed exceeds 1.5 m/s (300 ft/min).
| 1 | Smoke and rate-of-rise heat. Two detectors in one unit, with OR output. |
|---|---|
| 2 | NC/NO relay output. Set by jumper, 1 A / 30 V DC or 0.5 A / 125 V AC. |
| 3 | Status LED. Flashes in standby, steady in alarm. |
| 4 | Dual EN certification. EN 54-7 (smoke) and EN 54-5 (heat). |
| 5 | Up to 30 detectors per loop. Base fits on a junction box. |
Technical specifications
SD119-4H-12
| DETECTION | |
|---|---|
| Smoke detection | Photoelectric |
| Smoke sensitivity | 0.08–0.14 dB/m (EN) |
| Heat detection | Rate-of-rise: 57 °C (135 °F) or a rise of 8.3 °C/min (15 °F/min), Class A2 |
| Logic | Smoke OR heat |
| Processing | Advanced detection algorithms |
| OUTPUTS AND INDICATIONS | |
| Wiring | 4-wire, relay output |
| Contact mode | NC/NO by jumper (factory NO) |
| Relay rating | 1 A / 30 V DC, 0.5 A / 125 V AC |
| LED | Flashes every 1–3 s in standby, steady in alarm |
| POWER | |
| Supply voltage | 12 V DC (10–13.8 V) |
| Standby current | 80 µA |
| Alarm current | 30 mA |
| Start-up time | Up to 30 s |
| INSTALLATION | |
| Detectors per loop | Up to 30 |
| Position | Ceiling ≥ 15 cm from a wall, or wall 10–30 cm below the ceiling |
| Air speed | Up to 1.5 m/s (300 ft/min) |
| ENVIRONMENT AND MECHANICAL | |
| Operating temperature | −10 to +50 °C |
| Humidity | 0–95 % RH, non-condensing |
| Dimensions | Ø100 × 46 mm with base |
| Weight | 130 g with base |
| CERTIFICATION | |
| Standards | EN 54-7 (smoke), EN 54-5 (heat), UL 268 |
Documents
6 PDF files · English
| Type | TITLE | LANGUAGE | FORMAT | Open |
|---|---|---|---|---|
| ManualSD119-4H-12 - Manual EN.pdf | English | PDF · 0.3 MB | Download the file Manual | |
| DatasheetSD119-4H-12 - Datasheet.pdf | — | PDF · 0.1 MB | Download the file Datasheet | |
| DatasheetSD119-4H-12 - Datasheet EN.pdf | English | PDF · 0.3 MB | Download the file Datasheet | |
| Certificate of constancy of performanceSD119-4H-12 - Certificate of constancy of performance.pdf | English | PDF · 0.1 MB | Download the file Certificate of constancy of performance | |
| Certificate ULSD119-4H-12 - Certificate UL.pdf | English | PDF · 0.1 MB | Download the file Certificate UL | |
| Certificate KitemarkSD119-4H-12 - Certificate Kitemark.pdf | English | PDF · 3.4 MB | Download the file Certificate Kitemark |