Description
Conventional fire call point for conventional fire panels, reset with a key with no glass to break. Certified to EN 54-11 (LPCB).
| Type | Conventional, resettable element |
|---|---|
| Reset | Key reset, no glass to break |
| Alarm indication | Red LED and yellow-black flag |
| Operating voltage | 19–30 V DC |
| Certification | EN 54-11 (LPCB) |
| Dimensions | 84 × 84 × 45 mm |
Product description
IC0020 · Inim
Conventional fire call point for conventional fire panels, reset with a key with no glass to break. Certified to EN 54-11 (LPCB).
The IC0020 is a conventional manual call point for indoor use. Pressing the black spot on the transparent plastic front element raises the alarm in the same way as a break-glass unit, but nothing breaks. The alarm is shown by a steady red LED and by a yellow-black striped flag that drops into view at the top of the front plate.
It is reset with the plastic key: insert it in the slot, push the mechanism up and turn the key clockwise until it locks; the flag then withdraws and the LED goes off. Two keys are supplied, which are also used to open the housing.
It connects to the fire panel with 2 wires and runs on 19–30 V DC. A jumper selects the alarm resistance (RL or RH) to suit the panel. It is surface-mounted on the supplied back box; flush mounting needs the FCP0020 bracket. For outdoor use it must be fitted inside a suitable weatherproof box.
| 1 | No glass to break. Resettable element, key reset. |
|---|---|
| 2 | Alarm indication. Red LED and yellow-black flag. |
| 3 | Selectable alarm resistance. Jumper RL (260 Ω) or RH (660 Ω). |
| 4 | EN 54-11 (LPCB). For conventional fire panels. |
| 5 | Surface or flush. Surface back box supplied, flush with the FCP0020. |
Technical specifications
IC0020
| GENERAL | |
|---|---|
| Type | Conventional manual call point, resettable |
| Activation | Press the black spot on the front |
| Reset | Plastic key |
| Alarm indication | Steady red LED, yellow-black flag |
| ELECTRICAL | |
| Operating voltage | 19–30 V DC |
| Alarm resistance (“+” / “−”) | 260 Ω (RL) or 660 Ω (RH), by jumper |
| Connection | 2 wires to the fire panel |
| CERTIFICATION | |
| Standard | EN 54-11 (LPCB) |
| Certificate | 0832-CPR-F0442 |
| INSTALLATION AND ENVIRONMENT | |
| Mounting | Surface; flush with the FCP0020 bracket |
| Location | Indoor |
| Operating temperature | −5 to +40 °C |
| Humidity | 95% RH non-condensing |
| MECHANICAL AND PACKAGE | |
| Dimensions (H × W × D) | 84 × 84 × 45 mm |
| Weight | 126 g |
| Contents | Call point with surface back box, two keys |
| Accessories (sold separately) | WCP0020 clear cover, FCP0020 flush-mount bracket, DBCP0020 deep box for surface conduit, KCP0020 key |
Documents
6 PDF files · English
| Type | TITLE | LANGUAGE | FORMAT | Open |
|---|---|---|---|---|
| ManualIC0020 - Manual EN.pdf | English | PDF · 0.7 MB | Download the file Manual | |
| DatasheetIC0020 - Datasheet.pdf | — | PDF · 0.1 MB | Download the file Datasheet | |
| Declaration of conformityIC0020 - Declaration of conformity.pdf | — | PDF · 0.1 MB | Download the file Declaration of conformity | |
| Declaration of performanceIC0020 - Declaration of performance.pdf | — | PDF · 0.2 MB | Download the file Declaration of performance | |
| Certificate CPAIC0020 - Certificate CPA EN.pdf | English | PDF · 0.2 MB | Download the file Certificate CPA | |
| Certificate of constancyIC0020 - Certificate of constancy EN.pdf | English | PDF · 0.1 MB | Download the file Certificate of constancy |