Description
Mean Well switching power supply with 12 V backup battery charging (UPS function), 13.8 V / 5.4 A (74.5 W) output and an AC OK / AC Fail signal.
| Output voltage / current | 13.8 V / 5.4 A |
|---|---|
| Power | 74.5 W |
| Input voltage | 85–264 V AC |
| Battery | 12 V, charging and automatic changeover |
| Signal | AC OK / AC Fail |
| Dimensions | 159 × 97 × 38 mm |
Product description
SCP-75-12 · Mean Well
Mean Well switching power supply with 12 V backup battery charging (UPS function), 13.8 V / 5.4 A (74.5 W) output and an AC OK / AC Fail signal.
The SCP-75-12 is a Mean Well SCP-75-series switching power supply for systems that must keep working without mains power, such as alarm control panels and access controllers. It powers the load at 13.8 V and at the same time charges a 12 V backup battery connected to the B+ / B− terminals. When mains power fails, the load runs from the battery.
Terminal L gives a mains status signal to the panel: with mains present (AC OK) it carries the output voltage plus 0.2–0.7 V, on mains failure (AC Fail) it drops to 0 V. An NTC thermistor (not included) can be connected to CN2 for temperature compensation of the charging voltage; without a sensor the charger works normally. A potentiometer sets the output from −5% to +15% (13.1–15.9 V).
It accepts 85–264 V AC and is protected against short circuit and overload (hiccup mode, automatic recovery), output over-voltage (16.6–19.3 V, output shut down) and reversed battery connection, by fuse. It works from −20 to +60 °C, with load derating at high temperatures.
| 1 | UPS function. Powers the load and charges a 12 V battery. |
|---|---|
| 2 | AC OK / AC Fail signal. Tells the panel when mains power fails. |
| 3 | Temperature compensation. Charging voltage via NTC thermistor (not included). |
| 4 | Adjustable output. From −5% to +15% of the rated voltage. |
| 5 | Protection. Short circuit, overload, over-voltage, reversed battery. |
| 6 | Input 85–264 V AC. Wide input range, also 120–370 V DC. |
Technical specifications
SCP-75-12
| INPUT | |
|---|---|
| Input voltage | 85–264 V AC · 120–370 V DC |
| Frequency | 47–63 Hz |
| Input current (typical) | 1.5 A at 115 V AC · 0.9 A at 230 V AC |
| Inrush current (typical) | 45 A (cold start) |
| Efficiency (typical) | 80% |
| OUTPUT | |
| Output voltage / current | 13.8 V / 0–5.4 A |
| Peak current (5 s) | 6.5 A |
| Rated power | 74.5 W |
| Output voltage adjustment | −5% to +15% (13.1–15.9 V) |
| Voltage tolerance | ±2.0% |
| Hold-up time (typical) | 50 ms at 230 V AC, full load |
| BATTERY AND SIGNALS | |
| Battery | 12 V, on terminals B+ / B− |
| Temperature compensation | NTC thermistor on CN2 (not included) |
| Mains status signal (L) | AC OK: output voltage +0.2–0.7 V · AC Fail: 0 V |
| Fuses | Input F4A/250V (FS1) · battery F10A/250V (FS2) |
| PROTECTION | |
| Overload | 6.5–8.7 A, hiccup, automatic recovery |
| Output over-voltage | 16.6–19.3 V, output shut down, recovers when power is reapplied |
| Battery | Reversed connection, by fuse |
| Isolation withstand voltage | Input–output 3 kV AC |
| Safety standards | UL 62368-1, CB (IEC 62368-1), EAC TP TC 004 |
| MECHANICAL AND ENVIRONMENT | |
| Operating temperature | −20 to +60 °C (with derating) |
| Operating humidity | 20–90% RH non-condensing |
| Vibration | 2G, 10–500 Hz |
| Dimensions (L × W × H) | 159 × 97 × 38 mm |
| Weight | 0.5 kg |
Documents
2 PDF files · English
| Type | TITLE | LANGUAGE | FORMAT | Open |
|---|---|---|---|---|
| DatasheetSCP-75-12 - Datasheet EN.pdf | English | PDF · 0.6 MB | Download the file Datasheet | |
| Declaration of conformitySCP-75-12 - Declaration of conformity EN.pdf | English | PDF · 0.6 MB | Download the file Declaration of conformity |