Description
Plug-on Ethernet module for the Vision-X, Vision-XIP and MyAlarm-XIP panels: IP reporting to an alarm receiving centre (ARC), MyAlarm Cloud connection and VisionLink programming, locally or remotely.
| Path | Ethernet RJ45, 10BASE-T / 100BASE-TX (auto sensing) |
|---|---|
| ARC reporting | SIA IP, CSV IP, MyAlarm IP |
| Cloud | MyAlarm Cloud |
| Programming | VisionLink over IP, local or remote |
| Encryption | 128-bit AES |
| Compatible panels | Vision-X, Vision-XIP, MyAlarm-XIP |
Product description
CM751 · Digiflex
Plug-on Ethernet module for the Vision-X, Vision-XIP and MyAlarm-XIP panels: IP reporting to an alarm receiving centre (ARC), MyAlarm Cloud connection and VisionLink programming, locally or remotely.
The CM751 plugs onto the control panel's expansion port header on three plastic standoffs and connects to the building's local network with a CAT 5E cable. It is powered by the panel and takes 60 mA from the 12 V accessory power available. The panel supervises the module continuously and reports a trouble when communication with it is lost.
It sends alarm signals to the ARC over IP in SIA IP, CSV IP or MyAlarm IP, using little bandwidth. The link is supervised by poll messages at an interval you set, and data can be encrypted with 128-bit AES. You can set the Ethernet path for reporting destination 1, 2 or both. It also connects the system to MyAlarm Cloud.
With the VisionLink software you upload and download programming, review the event history and operate outputs and areas, on the local network or remotely over the internet, using TCP (default) or UDP. Remote access needs port forwarding on the router (default port 7701); where the public IP address changes, the panel is found through MyAlarm Cloud by the module's MAC address. Seven LEDs on the board show the module's status and network activity.
| 1 | Plug-on. Fits directly on the panel's expansion port, with no bus wiring. |
|---|---|
| 2 | ARC reporting. Over IP: SIA IP, CSV IP and MyAlarm IP, with link supervision (polling). |
| 3 | Encryption. 128-bit AES on the transmission to the ARC. |
| 4 | MyAlarm Cloud. Connects the system to the MyAlarm service. |
| 5 | VisionLink over IP. Programming, event history and control of outputs and areas, locally or remotely. |
| 6 | IP address. Static or by DHCP; a static or reserved address on the router is recommended. |
Technical specifications
CM751
| COMMUNICATION | |
|---|---|
| Network interface | Ethernet RJ45, 10BASE-T / 100BASE-TX, auto sensing |
| ARC reporting | Over IP: SIA IP, CSV IP, MyAlarm IP; also Conettix / Conettix NNC |
| Reporting destinations | Ethernet on destination 1, 2 or both |
| Link supervision | Poll messages at an interval you set (default 30 s) |
| Encryption | 128-bit AES (Rijndael) |
| Bandwidth | Low usage |
| Network protocols | UDP/IP, TCP/IP, Telnet, ICMP, SNMP, DHCP, BOOTP, TFTP, Auto IP, SMTP, HTTP |
| IP address | Static or by DHCP |
| REMOTE ACCESS | |
| Cloud | MyAlarm Cloud |
| Programming | VisionLink over IP, local or remote |
| Connection protocol | TCP (default) or UDP |
| VisionLink port | 7701 (default) |
| Dynamic public IP | Panel located through MyAlarm Cloud by MAC address |
| Access restriction | Can accept connections from one IP address only |
| INDICATORS | |
| Board LEDs | STATUS, RX, TX, POLL, REPORT |
| RJ45 socket LEDs | Link / data activity and full / half duplex |
| POWER AND INSTALLATION | |
| Supply | 12 V from the panel |
| Current | 60 mA |
| Mounting | Plug-on to the panel's expansion port, on 3 plastic standoffs |
| Compatible panels | Vision-X (firmware V2.10 or later), Vision-XIP, MyAlarm-XIP |
| Software | VisionLink V2.01 or later |
| Package contents | CM751 module, 3 plastic standoffs, HW750 riser kit (for use with the CM101 voice module) |
| MECHANICAL | |
| Dimensions | 93 × 52 × 30 mm |
| Operating temperature | 0 to +55 °C |
| Operating humidity | 5–85% at 30 °C, non-condensing |
Documents
3 PDF files · English and Greek
| Type | TITLE | LANGUAGE | FORMAT | Open |
|---|---|---|---|---|
| Installation manualCM751 - Installation manual EN.pdf | English | PDF · 3.8 MB | Download the file Installation manual | |
| DatasheetCM751 - Datasheet EN.pdf | English | PDF · 2.6 MB | Download the file Datasheet | |
| Network setup guideCM751 - Network setup guide GR.pdf | Greek | PDF · 0.9 MB | Download the file Network setup guide |